Verify wire fill percentage for NEC and utility code compliance — prevent overheating and failed inspections.
NEC 2020/2023 Chapter 9 Table 1 limits apply
Internal area per NEC Chapter 9 Table 4
Cross-sectional area includes insulation (NEC Annex C)
Include all current-carrying conductors AND grounding wires
Asymmetric wire can shift; larger margin prevents insulation damage
Two wires wedge together — pulling tension spikes without clearance
Standard multi-wire installation; extra space for heat dissipation
Uses: Dry indoor, commercial & residential
✓ Lightest metal option, doubles as ground path
✗ Not suitable for direct burial or wet locations
½" internal area: 0.211 in²
¾" internal area: 0.533 in²
Uses: Wet, outdoor, corrosive areas
✓ Stronger than EMT, weather/corrosion resistant
✗ Heavier and more expensive than EMT
½" internal area: 0.342 in²
¾" internal area: 0.586 in²
Uses: Underground, concrete encasement
✓ Corrosion-proof, lowest cost material
✗ Temperature-sensitive, no grounding path
½" internal area: 0.217 in²
¾" internal area: 0.508 in²
Where is the total cross-sectional area of all conductors (including their insulation), and is the conduit's internal area from NEC Chapter 9 Table 4. For example, three #12 THHN wires () in ¾" EMT (0.349 in²) gives — well within the 40% limit.
The NEC limits aren't arbitrary — they come from physics. Conductors carrying current generate heat, and that heat needs somewhere to go. Pack a conduit too full and you create an insulated bundle that can't shed heat fast enough, degrading insulation and potentially starting fires. The 40% rule for 3+ wires also leaves room to pull wires without excessive tension that could nick insulation against the conduit's inner wall.
Fill percentage is only half the story. When you run more than 3 current-carrying conductors in a single conduit, NEC 310.15(C)(1) requires you to derate the ampacity of each conductor. At 4–6 conductors you multiply ampacity by 0.80; at 7–9 conductors, by 0.70. This means a 12 AWG wire rated 20 A might only be allowed to carry 16 A in a shared conduit. Always run both calculations.
Electricians typically target 25–35% fill — not the full 40% — to allow pulling lubricant to work effectively and to make future wire additions easier. If you're right at the 40% limit, step up one conduit size. The material cost difference between ¾" and 1" conduit is small; a failed inspection or a heat-damaged wire job is not.
| AWG | Area (in²) | ½" (0.211) | ¾" (0.349) | 1" (0.581) | 1¼" (0.922) |
|---|---|---|---|---|---|
| 14 AWG | 0.0139 | 6 | 10 | 16 | 26 |
| 12 AWG | 0.0181 | 4 | 7 | 12 | 20 |
| 10 AWG | 0.0243 | 3 | 5 | 9 | 15 |
| 8 AWG | 0.0366 | 2 | 3 | 6 | 10 |
| 6 AWG | 0.0507 | 1 | 2 | 4 | 7 |
| 4 AWG | 0.0824 | 1 | 1 | 2 | 4 |
Values assume 40% fill limit (3+ conductors). For 1 conductor use 53%; for 2 conductors use 31%.