MathIsimple
NEC Chapter 9 · Electrical Code

Conduit Fill Calculator

Verify wire fill percentage for NEC and utility code compliance — prevent overheating and failed inspections.

100% FreeNEC CompliantCode VerificationSafety First
Conduit Fill Calculator
Select conduit size, wire gauge, and number of conductors

NEC 2020/2023 Chapter 9 Table 1 limits apply

Internal area per NEC Chapter 9 Table 4

Cross-sectional area includes insulation (NEC Annex C)

Include all current-carrying conductors AND grounding wires

NEC Chapter 9 Table 1 — Fill Limits at a Glance
Maximum conductor fill percentages for all conduit types
1 Conductor53% max
53%
47% empty

Asymmetric wire can shift; larger margin prevents insulation damage

2 Conductors31% max
31%
69% empty

Two wires wedge together — pulling tension spikes without clearance

3+ Conductors40% max
40%
60% empty

Standard multi-wire installation; extra space for heat dissipation

⚡ Note: The NEC counts 4+ conductors at the same 40% limit as 3 — the jump down to 31% only applies when you have exactly 2 wires. Always count ground wires toward fill.
Conduit Types — EMT vs. IMC vs. PVC
Different conduit types, same fill rules — but different internal areas for the same trade size
EMT

Electrical Metallic Tubing

Uses: Dry indoor, commercial & residential

Lightest metal option, doubles as ground path

Not suitable for direct burial or wet locations

½" internal area: 0.211 in²

¾" internal area: 0.533 in²

IMC

Intermediate Metal Conduit

Uses: Wet, outdoor, corrosive areas

Stronger than EMT, weather/corrosion resistant

Heavier and more expensive than EMT

½" internal area: 0.342 in²

¾" internal area: 0.586 in²

PVC

Polyvinyl Chloride

Uses: Underground, concrete encasement

Corrosion-proof, lowest cost material

Temperature-sensitive, no grounding path

½" internal area: 0.217 in²

¾" internal area: 0.508 in²

1The Fill Percentage Formula

Fill %=AwiresAconduit×100\text{Fill \%} = \frac{\sum A_{\text{wires}}}{A_{\text{conduit}}} \times 100

Where Awires\sum A_{\text{wires}} is the total cross-sectional area of all conductors (including their insulation), and AconduitA_{\text{conduit}} is the conduit's internal area from NEC Chapter 9 Table 4. For example, three #12 THHN wires (3×0.0181=0.0543 in23 \times 0.0181 = 0.0543\text{ in}^2) in ¾" EMT (0.349 in²) gives (0.0543/0.349)×100=15.6%(0.0543 / 0.349) \times 100 = 15.6\% — well within the 40% limit.

2Why These Limits Exist

The NEC limits aren't arbitrary — they come from physics. Conductors carrying current generate heat, and that heat needs somewhere to go. Pack a conduit too full and you create an insulated bundle that can't shed heat fast enough, degrading insulation and potentially starting fires. The 40% rule for 3+ wires also leaves room to pull wires without excessive tension that could nick insulation against the conduit's inner wall.

3Derating — The Hidden Companion Rule

Fill percentage is only half the story. When you run more than 3 current-carrying conductors in a single conduit, NEC 310.15(C)(1) requires you to derate the ampacity of each conductor. At 4–6 conductors you multiply ampacity by 0.80; at 7–9 conductors, by 0.70. This means a 12 AWG wire rated 20 A might only be allowed to carry 16 A in a shared conduit. Always run both calculations.

4Practical Sizing Tips

Electricians typically target 25–35% fill — not the full 40% — to allow pulling lubricant to work effectively and to make future wire additions easier. If you're right at the 40% limit, step up one conduit size. The material cost difference between ¾" and 1" conduit is small; a failed inspection or a heat-damaged wire job is not.

Quick Reference — Wire Areas & Conduit Capacity
THHN/THWN wire areas (NEC Annex C) — how many wires fit at 40% fill
AWGArea (in²)½" (0.211)¾" (0.349)1" (0.581)1¼" (0.922)
14 AWG0.01396101626
12 AWG0.0181471220
10 AWG0.024335915
8 AWG0.036623610
6 AWG0.05071247
4 AWG0.08241124

Values assume 40% fill limit (3+ conductors). For 1 conductor use 53%; for 2 conductors use 31%.

Wire Pulling Best Practices
  • Stay at 25–35% fill to make pulling easier
  • Use UL-listed wire pulling lubricant
  • Pull all conductors simultaneously — never one at a time
  • Keep bends to ≤360° total between pull points
  • Install conduit before pulling wires whenever possible
  • Use pulling eyes, not knots, on large conductors
Common Code Violations
  • Exceeding 40% fill to save on conduit cost
  • Forgetting to count ground wires in the fill total
  • Using wire areas for the wrong insulation type
  • Mixing wire types without recalculating fill
  • Skipping ampacity derating for 4+ conductors
  • Using EMT in wet/outdoor locations without approval

Frequently Asked Questions

Conduit fill percentage is the ratio of total wire cross-sectional area (including insulation) to the conduit's internal area, expressed as a percent. NEC Chapter 9 Table 1 limits it to 53% for 1 conductor, 31% for 2 conductors, and 40% for 3 or more conductors — to allow heat dissipation and safe wire pulling.
Ask AI ✨
Conduit Fill Calculator - Check NEC/Utility Compliance | MathIsimple